INFICON
INFICON FLUE-Mate Combustion Analyzer
Pickup available at 36 Enterprise Drive
Usually ready in 24 hours
INFICON FLUE-Mate Combustion Analyzer
502-202-G1
FLUE-Mate is the all-in-one combustion analyzer built to improve your combustion efficiency and safety. In addition to combustion analysis, this tool is also equipped with an integrated manometer, thermometer, ambient CO test, cracked heat exchanger test and provides draft analysis. FLUE-Mate features intuitive mode selection and navigation, 15 programmable fuel selections and field-replaceable O2 sensor, probe and water trap
to minimize downtime. Download the FLUE-Mate app to generate quick analysis reports on your smart phone or tablet. FLUE-Mate is the user-friendly, comprehensive combustion analyzer for all your heating jobs.
Features:
- Easy-to-read backlit LCD display
- Displays efficiency, O2, CO2, CO and flue gas temperature readings all on one screen
- Field-replaceable O2 sensors to minimize downtime
- Automatic CO sensor protection
- FLUE-Mate app allows you to store and email reports
- Monitor system pressures with built-in manometer and hose kit
- External water trap prevents internal electronic and sensor damage
- Optional Bluetooth® printer
- Upgradeable to measure NOx
Specifications:
- Includes: FLUE-Mate, Flue gas probe with 5 ft (1.5m) dual hose, manometer pressure hose, water trap, AC wall charger, Carrying case
- Power source: Lithium ion battery (rechargeable)
- Battery life: 8 hours
- Weight: 0.77 lb (349 g)
- Compatible fuels: Natural gas, Propane, Fuel oil (#2, #4, or #6), Diesel, Wood, Coal, Bio-fuel 5%, L.P.G., Butane, Bagasse, B100
- Measured O2: Range: 0 ~ 25.0% vol, Resolution 0.1% vol, Accuracy ±0.2% vol
- Measured CO high immunity H2 with NOx filter: Range 0 - 4000 ppm, Resolution 1 ppm, Accuracy ±20 ppm 0 - 400 ppm, ±5% measured value 401 - 4000 ppm
-
Measured Air Temperature: Range -20.0 - 120.0°C, Resolution 0.1°C, Accuracy ±1°C
- Flue Gas Temperature: Range -20.0 - 800.0°C, Resolution 0.1°C , Accuracy ±1% measured value 212.2 - 1472°F (101-800°C)
- Pressure (draft and differential) Range -40.0 - +80.0 in. H2O, Resolution 0.004 in. H2O, Accuracy: ±1% measured value @ -40.0 - -0.81 in. H2O,±0.008 in. H2O @ -0.80 - +0.80 in. H2O, ±1% measured value @ +0.81 - +80.0 in. H2O
-
Calculated Values:
-
CO2 0 - 99.9% vol 0.1% vol Temperature differential 32.0 - 1472.0°F
0 - 800.0°C0.2°F
0.1°CAir index 0.00 - 9.50 0.01 Excess air 0 - 850% 1% Stack losses 0.0 - 100.0% 0.1% Effeciency 0.0 - 120.0% 0.1%
-